GENERAL
SPECIFICATION
The specification for the parts of this
contract mentioned below cover design, manufacture, assembly and
testing at the
manufacturer’s factory as well
as the supply,
delivery, installation, testing and commissioning of the cable at site.
CLIMATIC
CONDITIONS
The climate is tropical and has marked
Monsoon character with seasonal changes from humid, warm, rainy season, summers
to cool and dry winters. Maximum temperature occurs during the period from
April to May reaching approximately 43 deg. C
(110 deg. F) with a relative air humidity of 60% to 70%.
The annual mean temperature is approximately
29 deg. C (84 deg. F). During the rainy monsoon month from June to September,
the average relative air humidity is 80% and reaches extreme values up to
saturation point during longer periods. The annual rainfall, most of which
occurs from June to September is 2000mm to 2500mm.
OPERATING
CONDITIONS
The cable will be connected to the 11KV or
415 volts 3-phase or 220 volt single phase, 50 Hz Bus of Power Development
Board/REB/ DPDC/DESCO Bangladesh.
STANDARDS
All equipment and materials must be in
conformity with the most recent relevant Bangladeshi laws, standard rules and
regulation. Particular attention is to be paid to the Electrical Act 1910 and
Electricity Rules 1937 (as amended in 1946). All equipment and materials to be
supplied which required any form of approval by the Bangladesh Government or a
Local Authority like PDB/ DPDC/DESCO or REB must satisfactorily pass all
inspection and tests procedures imposed by them.
Otherwise, all the equipment and materials
must be in conformity with the most recent international rules, regulation,
standards and recommendation: IEC.
STANDARD
DATA
The following standard values for high and
low voltage are standard in Bangladesh.
Distribution bus High Voltage : 11KV,
Maximum system High Voltage : 12 KV.
Distribution bus Low Voltage : 415/240 V
FREQUENCY
The standard power frequency in Bangladesh
will be: 50Hz.
DESIGN
& CONSTRUCTION REQUIREMENTS
All Cables are to be in accordance with the
latest recognized rules of workmanship and modern engineering practice and must be
suitable in every respect for continuous operation at maximum output under the
climatic conditions as specified above.
MATERIAL
REQUIREMENTS
Conducting materials for cables must be of
99.99% pure annealed stranded copper and insulation of thermoplastic materials
based on PVC or XLPE for HT and LT Cables shall be complying with relevant
IEC/VDE/BS/BDS standards.
PROPERTIES
OF PVC COMPOUND
1. Tensile
Strength
Thermoplastic PVC compound
|
Tensile Strength
|
||
Before Ageing (kgf) min
|
After Ageing at 80+2◦C for 7 days (kgf) min
|
Difference after ageing % max
|
|
Insulation mixture ( LT Cables)
|
125
|
125
|
25
|
Insulation mixture ( HT Cables)
|
150
|
150
|
25
|
Sheath mixture
|
100
|
100
|
25
|
2.
Elongation
Thermoplastic PVC compound
|
Elongation
|
||
Before Ageing
% min
|
After Ageing at 80+2◦C for 7 days % min
|
Difference after ageing % max
|
|
Insulation mixture ( LT Cables)
|
125
|
125
|
25
|
Insulation mixture ( HT Cables)
|
100
|
100
|
25
|
Sheath mixture
|
150
|
150
|
25
|
3. Thermal
Stability at 200◦C
Thermoplastic PVC compound
|
Thermal Stability at 200◦C
|
|||||
Volume resistivity at 70◦C Ohm.cm
|
Before Ageing
% min
|
After Ageing
% min
|
Deformation under pressure at 70◦C. Depth
of indentation % max
|
Heat Shock at 150◦C
|
Shrinkage at 150◦C % max
|
|
Insulation mixture ( LT Cables)
|
10
|
80
|
80
|
50
|
No Crack
|
4
|
Insulation mixture ( HT Cables)
|
10
|
120
|
120
|
50
|
No Crack
|
4
|
Sheath mixture
|
-
|
40
|
40
|
50
|
No Crack
|
-
|
MARKING
AND CODE
The Cables shall be marked and coded in
accordance with BS, IEC, VDE or equivalent standards.
INSULATION
CO-ORDINATION
The insulation of thermoplastic materials
based on PVC or XLPE for HT and LT Cables shall be comply with relevant
IEC/VDE/BS/BDS standards.
The insulation test voltage for Cables is as
follows:
Rated voltage of the cables, KV
|
Single phase test voltage, KV
|
Three phase test voltage, KV
|
Direct test voltage, KV
|
0.6
|
4
|
4
|
12
|
3.5
|
11
|
11
|
33
|
5.8
|
17
|
17
|
51
|
TECHNICAL
REQUIREMENTS
The Cable specified in the following items
shall withstand the impulse levels and test voltages specified by the
recommendations of IEC, as stipulated before. They must be capable of carrying
the short time current for three seconds and must withstand the short circuit
(Peak value) current.
The cable must be designed accordingly in
order to withstand the mechanical short circuit stresses.
They must contain all technical particulars
which are mentioned in the Schedule of Technical Data.
The Owner reserves the right to have routine
tests carried out on each type of equipment at the manufacturer’s factory in
the presence of his representative.
The single bars shall be marked by the colors as
per IEC, VDE or BS standard.