How Much Current  can carry different types of cable

CROSS SECTION
NO./DIA OF WIRE
BYA
BYM
BYFYE
NYY
NYFGbY
NYSEYFGbY
XLPE
1 -Core
1-Core
2-Core
3/4-Core
2-Core
1-Core
2-Core
3/4-Core
3/4-Core
3-Core
3-Core
mm2
mm
C
S
C
S
C
S
C
S
C
S
C
S
C
S
C
S
U/G
A
U/G
A
U/G
A
1.0 RE
1/1.13
13
16
13
16
1
15
11
12
13
15
-
-
-
-
-
-
1.5 RE
1/1.38
16
20
16
20
16
18
15
16
16
18
27
22
25
19
22
16
2.5 RE
1/1.78
22
28
22
28
22
26
20
22
22
26
36
30
34
27
30
23
4 RM
7/0.85
30
37
30
37
30
33
27
30
30
33
47
39
44
35
38
32
6 RM
71.04
38
47
43
47
37
43
33
27
37
37
59
50
55
45
45
48
10 RM
7/1.35
52
63
52
63
50
60
46
51
78
69
74
62
64
56
16 RM
7/1.70
70
85
70
85
66
80
58
67
100
94
97
84
83
75
83
75
79
79
100
105
25RM/SM
7/2.14
91
110
91
110
75
88
66
77
130
125
125
110
110
98
110
98
100
100
120
140
35RM/SM
7/20/2.03
112
136
112
136
92
108
81
90
155
160
150
140
130
120
130
120
120
120
150
170
50RM/SM
19/20/1.83
136
164
185
195
155
150
155
150
140
145
180
200
70RM/SM
19/20/2.10
173
207
225
245
190
190
190
190
170
170
225
255
95RM/SM
19/20/2.52
216
253
270
300
225
230
225
230
200
220
260
305
120RM/SM
37/39/2.03
244
291
310
350
260
270
260
270
230
250
300
350
150RM/SM
37/39/2.27
-
333
350
405
295
305
295
305
260
290
330
400
185RM/SM
37/39/2.52
-
381
390
460
330
350
330
350
290
325
370
455
240RM/SM
61/39/2.24
-
452
450
555
385
410
385
410
200
220
430
530
300RM/SM
61/39/2.39
-
526
515
640
425
470
425
470
470
600
400RM/SM
61/2.89
-
639
585
770
480
530
525
675
500RM/SM
61/3.23
-
752
680
900
525
600
630RM/SM
127/2.52
-
855
800
1030
590
690

Note: C = Concealed;       S = Surface;      U/G=Under Ground ;           A  =Ambient  