LIGHTNING ARESTER
ESTIMATE |
Providing
& fixing 25.4 mm. (1") dia 457 mm. (1.5 ft) long solid copper rod
with sharp top end for arresting lightning securedly bonded with 6.6 mm.
thick 150 mm. x 150 mm. Copper base plate to be recessed in wall complete
with nuts, bolts, CC work etc.
|
Earthing
the electrical installation with 40
mm. (1.5") dia G.I. pipe (Earth electrode) having 6.35 mm. dia hole across the pipe at
305 mm. interval securedly bonded by soldering with 2 nos.of No2 SWG HDBC earth leads with its protection
by 20 mm. (3/4") dia G.I. pipe up-to plinth level run at a depth
of 609.6 mm. (2 ft.) below G.L.up-to main board to be earthed including
necessary connecting copper sockets, bolts, nuts, etc. complete for maintaining earth
resistance within 1 ohm.
|
a) Depth
of bottom of main electrode at 37338
mm. (122.5 ft) from GL & length of electrode 36576 mm. (120 ft).
|
Construction
of Earthing inspection pit inside measurement 600 mm x 600 mm with 250 mm
thick brick in cement morter (1:4) with 100mm thick RCC top slab (1:2:4) with
1% re-inforcement 450 mm dia water sealed CI man-hole cover with locking
arrangement including necessary earth works, site filling and one brick flat
soling 75 mm thick (1:3:6) base concrete for making inlet channel & 12mm
thick (1:2) cement plaster with neat finishing etc.all complete up to a depth
of .75 meter.
|
Providing
& drawing No-2 HDBC wire through 12.7 mm. (½") dia G.I. pipe
including fitting, fixing the G.I. pipe in wall or column complete as
required.
|