SUB STATION ESTIMATE

SUB STATION
 ESTIMATE
1
Providing following GI pole fabricated with GI pipe complete with GI sockets, M.S. base plate, top cover, necessary welding as required:-
a.
Total 10668 mm (35’'-0") long having 152.4 mm (6") dia 7620 mm (25') at the bottom, and 101.60 mm (4") dia 3048 mm (10') at the top with 609 mm x 609 mm x 6.35 mm (2'-0" x 2'-0" x 0’-0. 25") size steel base plate.
2
Nos.
2
Erection of following tubular pole upto 1828.80 mm (6’) depth by placing the pole base on one layer of Ist. class brick flat soling over 76.2 mm (3") sand bedding and making 1:2:4 C.C. work around the pole  304.8 mm (1'-0") below GL & 304.8 mm(1’ ft) above GL, 12.5 mm (1/2") thick cement plaster with neat cement finishing over concrete surface including proper curing, excavation & refilling and ramming the loose soil etc. as required.
a.
10668 mm (35’) long MS/GI /SpunP.C pole with 457.20 mm x 457.20 mm (1.5’x1.5’) cc work
2
Nos.
3
Providing & fixing U-channel iron cross-arm of size 38 mm x 76 mm x 38 mm x 6.35mm. (1.5" x 3" x 1.5" x 0.25") on single pole / H-pole with the help of necessary clamps, nuts, bolts etc. including making required no. of holes on the cross-arm for fixing of drop out fuse, lightning arrester including  two coats of superior quality aluminum painting over required prime coat of anti corrosive red-oxide painting  complete as required & as per instruction of the Engineer-in-charge.
20
Mtrs.
4
THREE PHASE OIL TYPE TRANSFORMER
Supply of following oil-immersed, natural air cooled, 3-phase, 50-Hz, 11KV/0.415 KV & 0.24 KV outdoor type distribution transformer  of DYN11 vector group complete with two windings of high conductivity copper having percentage impedance 4 - 6.5%, basic impulse insulation level 75 KV , Dielectric strength 28 KV (for 1 min),  HT & LV porcelain bushings, manual 5 position standard tap changer, conservator, thermometer, oil inlet & outlet valves, oil level indicator, dehydrating breather, lifting lugs, earthing terminals, wheel, data plate etc. in/c painting, suitable for operation at 40°C ambient temperature with maximum temperature rise 60°C, locally manufactured and tested in Bangladesh as per NEMA/VDE/IEC/BS standards: 
(a) Capacity: 1500/1600 KVA with buchholz relay.
(b) No load loss: 2200 watts (Maximum)
(c) Full load loss: 18000 watts (Maximum)
Manufactured by the valid ISO-9001 certified company having test certificate for the required or higher capacity of transformer   according to relevant IEC standards from BUET/CUET /DUET/ KUET/RUET.
1
No.
5
Installation, testing and commissioning of following 11 KV/.415KV  transformer on prepared platform  on pole / c.c. foundation with the help of necessary tools & plants. skilled labour & technician as per direction of the Engineer-in-charge.
a.
1250-1600 KVA3 phase transformer on C.C. pad
1
Job.
6
Supply of 11 KV, 3-phase, 50 Hz, indoor type, high tension switchgear complete with Vacuum/SF6 Circuit Breaker, 800 Amps hard-drawn electrolytic copper bus-bars, 1 No 0 - 15 KV range voltmeter & 1 no. ammeter of adequate range both with selector switch, 1 no. of panel heater with auto thermostat control switch, manual ON & OFF push button switch and ON-OFF-TRIP indicators including following components (components such as VCB, CT, PT, microprocessor controlled IDMT relay shall be manufactured   according to relevant NEMA/VDE/IEC/JIS/BS Standards and shall have type test certificate according to relevant IEC Standard)  assembled locally in 14 SWG sheet steel metal clad, dust & vermin proof, free standing, floor mounting, epoxy resin powder  coat painted cabinet as per relevant IEC standards and as per approval & acceptance of the Engineer.
With withdrawable type Vacuum/SF6 Circuit Breaker.
(i)
1 Set of 11KV, 630 Amps  (20KA), 3-phase, 50 Hz, trolley mounted fully withdrawable type Vacuum/SF6 Circuit Breaker complete with motor operated spring charged stored energy mechanism for auto tripping at 12/24/48/110 volts D.C (without battery)
(ii)
2 Nos. 11 KV, cast resin insulated, dry type; double pole PT having ratio 11/0. 11, burden 50VA, class 0.5 for metering &  protection.
(iii)
3 Nos. 11 KV cast resin insulated, dry type, double core CT of adequate current ratio (compatible with the transformer capacity), burden 10-15 VA, first core of class 0.5 M5 for metering and second core of class 10P10 for protection.
(iv)
1 No of Triple pole solid-state microprocessor control IDMT relay with 2 elements of over current and short circuit protection and one for earth fault protection.
(v)
1 No. 415V, 6A (10KA) TPMCB for PT secondary protection.
Assembled by the valid ISO-9001 certified company having test certificate according to relevant IEC standards from BUET/CUET/DUET/KUET/RUET.
1
No.
7
Installations, testing and commissioning of following 11 KV, 50 Hz. 3-phase, indoor type  HT switchgear on prepared foundation with the help of  necessary tools, plants, skilled labour & technician  as per direction of the Engineer-in-charge.
a.
With withdrawable type Vacuum/SF6 Circuit breaker
1
Job
8
LT SWITCH GEAR
Supply of 415 V, 3-phase, 50 Hz, indoor type low tension switch-gear of following specification complete with voltmeter (0 - 500V) & ammeter of adequate rating both with selector switch, indicating lamps for ON - OFF and following components (components such as TPMCCBs shall be manufactured   according to relevant NEMA/VDE/IEC/JIS/BS Standards and shall have type test certificate according to relevant IEC Standard)  assembled locally in 14 SWG sheet steel metal clad, dust & vermin proof, free standing, floor mounting, epoxy resin powder  coat painted cabinet as per relevant IEC standards and as per approval & acceptance of the Engineer.
For 1500 /1600 KVA Transformer:
INCOMING :
1 Set - 415V, 3000 amp. TP&NE hard drawn electrolytic copper busbar.
1 No.-415V, 2200A (80KA), adjustable type TPMCCB / ACB for main control with thermal overload & instantaneous electro-magnetic short circuit release.
3 Nos. -415V, 2500/5 ratio current transformer with suitable accuracy & burden.
OUTGOING :
1 No. - 415V, 1600A (80KA) adjustable type TPMCCB with instantaneous electro-magnetic short circuit release  (for PFI control).
1 No. - 415V, 600A (50KA) adjustable type TPMCCB with instantaneous electro-magnetic short circuit release.
2 Nos. - 415V, 400A (35KA) adjustable type TPMCCB with thermal overload & instantaneous electro-magnetic short circuit release.
4 Nos. - 415V, 300/320A (35KA) adjustable type TPMCCB with thermal overload & instantaneous electro-magnetic short circuit release.
1 No. - 415V, 250A (35KA) adjustable type TPMCCB with thermal overload & instantaneous electro-magnetic short circuit release.
2 Nos. - 415V, 200A (25KA) adjustable type TPMCCB with thermal overload & instantaneous electro-magnetic short circuit release.
1 No. - 415V, 100A (16KA) adjustable type TPMCCB with thermal overload & instantaneous electro-magnetic short circuit release.
 1 No. - 415V, 30/32A (16KA) TPMCCB with thermal overload & instantaneous electro-magnetic short circuit release.
Assembled by the valid ISO-9001 certified company having test certificate according to relevant IEC standards from BUET/CUET/DUET/KUET/RUET.
1
No.
9
POWER FACTOR IMPROVEMENT PANEL
Supply of following 415 volt, 3 phase, 50 Hz power factor improvement panel complete with TP busbars and earth block, micro processor controlled auto power factor correction relay with digital PF reading display, capacitor bank, contactor, fuse, ON indicators for every stage of capacitor bank (except directly connected one) etc. shall be manufactured & tested as per NEMA/VDE/IEC/JIS/BSS standards assembled locally   in 16 SWG sheet steel clad dust & vermin proof, free standing, floor mounting, epoxy resin  powder coat painted  cabinet. as per relevant IEC standards and as per approval & acceptance of the Engineer.
For 1500/1600  KVA Transformer
PFI Capacity- 900 KVAR
3 Nos.- 415V, 1800A hard drawn electrolytic copper busbar.
1 No. - 415V, 25 KVAR, 50 Hz TP power capacitor bank with built in / separate discharge coil for connection directly with line through fuse.
3 Nos.-415V, 25 KVAR, 50 Hz TP power capacitor bank with built in / separate discharge resistor.
4 Nos. - 415V, 50 KVAR, 50 Hz TP power capacitor bank with built in / separate discharge resistor.
6 Nos. - 415V, 100 KVAR, 50 Hz TP power capacitor bank with built in / separate discharge resistor.
3 Nos. - 415V, 40 Amps, 50 Hz   auto TP magnetic contactor with AC3 duty.
4 Nos. - 415V, 80 Amps, 50 Hz auto TP  magnetic contactor with AC3 duty.
6 Nos. - 415V, 160 Amps, 50 Hz auto TP magnetic contactor with AC3 duty.
12 Nos. - 415V, 50 Amps.  HRC fuse with base.
12 Nos. - 415V, 100 Amps.  HRC fuse with base.
18 Nos. - 415V, 200 Amps.  HRC fuse with base.
Assembled by the valid ISO-9001 certified company having test certificate according to relevant IEC standards from BUET/CUET/DUET/KUET/RUET.
1
No.
10
Installation, testing and commissioning of 415V, 3-phase, 50 Hz indoor type LT switchgear/P.F.I. plant suitable for following capacity transformer on prepared c.c. foundation with the help of necessary tools & plants, skilled labour & technician as per direction of the Engineer-in-charge.
a.
For 1250-1500 KVA. Transformer
2
Jobs.
11
Supply of outdoor type11 KV, 50 Hz, 100A, (10 KA), 75 KV BIL lightning arrester complete with mounting accessories etc. manufactured by GEM Co. Ltd, Bangladesh /ENERGYPAC or equivalent product of USA EU Countries (3 Nos. in a set).
1
Set.
12
Supply of outdoor type 11KV, 50 Hz, 5KA (20 KA) dropout fuse complete with mounting accessories etc. manufactured by GEM Co. Ltd, Bangladesh /ENERGYPAC or equivalent product of USA /EU Countries (3 Nos.  in a set).
1
Set.
13
Installation of  HT drop out fuse/ lightning arrester/ disconnection switch on prepared U-channel cross-arm on single / H-pole with necessary fixing materials complete as per instruction of the Engineer-in-charge.
a.
Drop out fuse.
1
Set.
b.
Lightning arrester.
1
Set.
14
Providing & laying of following sizes LT PVC insulated sheathed & armoured cable (NYFGbY)/ HT (11KV) PVC insulated, sheathed, screened & armoured cable (NYSEYFGbY)/HT (11KV) armoured XLPE Cable: All electrical contacts shall be of brass/copper  connected through connector or soldering ( no twisting shall be allowed) and cables shall be manufactured and tested according to  relavent IEC/BDS/ BS/ VDE  standards and as per detailed specification mentioned in Annexure-A. The work shall be carried out as per direction/approval/acceptance of the Engineer.
(a)
 In kutcha ground by cutting 45.70 cm width x 91.40 cm depth trench with necessary brick or tile protection and mending  the damages good by refilling trench with proper compaction.
(b)
 In pucca floor through  required size of PVC pipe cutting trench of necessary size and mending good the damages with one layer 1st class flat brick soling,75 mm thick (1:2:4) cc work with neat cement finishing etc.
(c)
In pucca ground/road through required size of PVC pipe by cutting 45.70cm width x 91.40 cm depth trench mending good the damages by earth refilling with proper compaction providing 50 mm thick compacted premix bituminous carpeting over one layer of 1st class flat brick soling and 75 mm thick compacted water bound macadam of khoa of brick.
With HT (11KV) Cables (NYSEYFGbY) manufactured by BRB/Paradise/BBS/ Poly/ Supersign or equivalent approved by the Engineering-in-Charge    
a) 3C x 185 sq.mm cable
i)
In kutcha ground
20
Mtrs.
ii)
In pucca floor through 125 mm PVC pipe having wall
 thickness of 3 mm.
60
Mtrs.
iii)
In pucca ground/pucca road through 125 mm PVC
pipe having wall thickness of 3 mm.
20
Mtrs.
15
Providing & laying of following additional PVC insulated & sheathed cable  (NYY) / XLPE  insulated & PVC sheathed cable (2XY)  with PVC insulated green/white coloured ECC wire (BYA) connecting at both ends, through GI pipe (National Tubes Ltd. Made or equivalent) in a common trench in pucca ground/pucca road. All electrical contacts shall be of brass/copper  connected through connector or soldering ( no twisting shall be allowed) and cables shall be manufactured and tested according to relavent IEC/BDS/ BS/ VDE   standards and as per detailed specification mentioned in Annexure-A. The work shall be carried out as per direction/approval/acceptance of the Engineer.
Cables manufactured by BRB/Paradise/BBS/Poly/ Supersign /Citizen (for both NYY & 2XY cable)/Evana/Khawaja /MEP ( for NYY only)  or equivalent approved by the Engineering-in-Charge
1C-4x600 sq.mm (NYY) with 600 sq.mm (BYA) ECC wire through GI pipe of minimum inner dia 125 mm. (For X-Former LT to L.T Switchgear  & PFI) (Each cable for 3  Nos Loop).
150
Mtrs.
16
Supply & fixing of heat shrink termination kit out-door / in-door use complete with DIN lugs earth connection hardware & cable preparation kit (In-door & outdoor) at the point of cable termination for 11 KV 3-core PVC insulated & PVC sheathed & armoured / non-armoured cable of the following sizes  (Made in GERMANY/ USA/UK/ FRANCE/ JAPAN/ITALY/ SWEDEN/ SWITZERLANDor equivalent approved by the Engineering-in-Charge
FOR  IN-DOOR  USE
a.
3 x 185 mm2
3
Kits
b.
3 x 150 mm2
1
Kit
17
Supplying and fixing of heat shrink self-amalgamating tape of the following sizes for bus-bar of both HT switch-gear (11 KV) & LT switch-gear / PFI, transformer terminals as protection against flash-over
a.
Width 100 mm thickness 1 mm
30
Mtrs.
18
Earthing the electrical  installation with 40 mm. (1.5") dia G.I. pipe (Earth electrode)  having 6.35 mm. dia hole across the pipe at 305 mm. interval securedly bonded by soldering with 2 nos.of No2 SWG  HDBC earth leads with its  protection  by 20 mm. (3/4") dia G.I. pipe up-to plinth level run at a depth of 609.6 mm. (2 ft.) below G.L.up-to main board to be earthed including necessary connecting copper sockets, bolts, nuts,  etc. complete for maintaining earth resistance within 1 ohm.
a.
Depth of bottom of main electrode at  37338 mm. (122.5 ft) from GL & length of electrode 36576 mm. (120 ft).
i) Lightning arrester
1
Set.
ii) H.T Meter
1
Set.
iii) H.T Switchgear
1
Set.
iv) X-Former Neutral
1
Set.
v) X-Former Body
1
Set.
vi) L.T Switchgear
1
Set.
vii) P.F.I
1
Set.
7
Sets.