Low voltage (less than 1000 VAC) types are common in domestic,
commercial and industrial application, include:
MCB
(Miniature Circuit Breaker)—rated current not more than 100 A. Trip characteristics
normally not adjustable. Thermal or thermal-magnetic operation. Breakers
illustrated above are in this category.
MCCB
(Molded Case Circuit Breaker)—rated current up to 1000 A. Thermal or
thermal-magnetic operation. Trip current may be adjustable in larger ratings.
Low
voltage power circuit breakers can be mounted in multi-tiers in LV switchboards
or switchgear cabinets.
The
characteristics of LV circuit breakers are given by international standards
such as IEC 947. These circuit breakers are often installed in draw-out
enclosures that allow removal and interchange without dismantling the
switchgear.
Large
low-voltage molded case and power circuit breakers may have electrical motor operators,
allowing them to be tripped (opened) and closed under remote control. These may
form part of an automatic transfer switch system for standby power.
Low-voltage
circuit breakers are also made for direct-current (DC) applications, for example
DC supplied for subway lines. Special breakers are required for direct current
because the arc does not have a natural tendency to go out on each half cycle
as for alternating current. A direct current circuit breaker will have blow-out
coils which generate a magnetic field that rapidly stretches the arc when
interrupting direct current. The 10 ampere DIN rail-mounted thermal-magnetic miniature circuit breaker is the most common
style in modern domestic consumer units and commercial electrical distribution boards throughout Europe. The design includes the following
components:
Actuator lever - used to manually trip and reset the
circuit breaker. Also indicates the status of the circuit breaker (On or
Off/tripped). Most breakers are designed so they can still trip even if the
lever is held or locked in the "on" position. This is sometimes
referred to as "free trip" or "positive trip" operation.
Actuator
mechanism - forces the contacts together or apart.
Contacts
- Allow current when touching and break the current when moved apart.
Terminals
Bimetallic
strip
Calibration
screw - allows
the manufacturer to precisely adjust the trip current of the
device after assembly.
Solenoid
Arc
divider / extinguisher
Shapes
and sizes can vary depending on the end user or switchgear manufacture. Typical
examples of low voltage single ratio metering current transformers are either
ring type or plastic moulded case. High-voltage current transformers are
mounted on porcelain bushings to insulate them from ground. Some CT
configurations slip around the bushing of a high-voltage transformer or circuit
breaker, which automatically centers the conductor inside the CT window.
The
primary circuit is largely unaffected by the insertion of the CT. The rated
secondary current is commonly standardized at 1 or 5 amperes. For example,
a 4000:5 CT would provide an output current of 5 amperes when the primary
was passing 4000 amperes. The secondary winding can be single ratio or multi
ratio, with five taps being common for multi ratio CTs. The load, or burden, of
the CT should be of low resistance. If the voltage time integral area is higher
than the core's design rating, the core goes into saturation towards the end of each cycle, distorting the
waveform and affecting occur.
Coupling: Connects with the prime mover to transmit power.
6. Bearing: Supports revolving parts for stable revolution
The
synchronous generator most commonly used, the revolving –armature type AC exciter
is installed on the shaft used for DC excitation of the field coil. The output
is converted to DC with the silicon rectifier for supply to the coil.
No. of
Revs. And Poles
The relation between revolution speed and frequency
in generators is represented by the following formula
No comments:
Post a Comment