Tuesday, August 12, 2014

Area Required for Transformer Room and Substation for Different capacities

Minimum Load Densities
Minimum Load Densities
Type of occupancy
Unit Load W/m2 Covered Area

Non A.C.
A.C.
Dwelling: single/multi families (other than Hotels)
25
100
Office Bldg/Commercial Multistoried Bldgs.
35
95
Hospitals
40
105
Schools/College
15
90
Large Storage Space, Ware House
2
_
Restaurants (Excluding Electric Cooking)
20
95
Industrial Bldgs(Excuding the loads for machine)
20

Hotel/Motel/appartment house (Without cooking loads of Tenants)
30
100
Banks
25
95
Barbar Shops & Beauty Parlours
40
100
Departmental Store
35
95
Parking area in Commercial Bldg
4


Area Required for Transformer Room and Substation for Different capacities
Capacity of Transformer
 (KVA)
Transformer Room Area
 (m2)
Total Sub-station Area(With H.T. , L.T., panels & transformer room but without Generator (m2)
1 x 150
12
42
1 x 250
13
45
2 x 250
26
90
1 x 400
13
45
2 x 400
26
90
3 x 400
39
135
2 x 630
26
90
3 x 630
39
135
2 x 1000
26
90
3 x 1000
39
135

Area Requirement for Stand by Generator Room

Area Requirement for Stand by Generator Room
Capacity (Kwatt)
Area (m2)
1 x 25
20
1 x 48
24
1 x 100
30
1 x 150
36
1 x 300
48
1 x 500
56
Note :
1)     Sub-Station equipment  and  Generator  shall  not be installed in Basement floor of any 
        building .
2)     A separate Sub-Station building is preferred for any project. Location of  Sub- Station            
        building  shall be at load center of the complex.